Attic ventilation calculator
Total NFA, the intake and exhaust split, feet of ridge vent.
Best overall — ridge vent, on any ridge long enough to carry the exhaust half alone.
Best on a short hip ridge — box vents, counted by NFA and set in one row near the peak.
Never — both on one attic. Every maker we read says one exhaust type only.
Our pick — Ridge vent: it ventilates the whole ridge through one opening, when the ridge is long enough
| Ridge vent | Box (static) vent | Turbine vent | |
|---|---|---|---|
| Net free area | 11–20 in² per ft | 38–60 in² each | 95 / 132 in² (12 / 14 in) |
| For 720 in² of exhaust | 40 ft at 18 in²/ft | 15 at 50 in² | 8 × 12 in |
| Where it sits | Continuous at the peak | Centre 2 ft (max 3) below ridge | Spot vent, high on the slope |
| Hole in the deck | Slot 3/4 in each side of centre | 8–9.5 in opening each | 12 or 14 in opening each |
| Works on a short hip ridge | |||
| No moving parts | |||
| Penetrations to flash | One, along the ridge | One per vent | One per vent |
| Safe to mix with another exhaust type |
The short answer to ridge vent vs box vent is that they are two ways of placing the same number — the exhaust half of the attic’s required net free area, which the code ties to 1/150 of the floor area. A ridge vent spreads it along the peak; box vents put it through a row of holes just below. Which one fits is mostly a question of how much ridge the roof has, which is why this page reads the numbers off the makers’ own sheets, and why the ventilation calculator is the place to start for your own attic.
Every attic vent is rated in net free area, the open area left once louvers, baffles and screen are taken out of the hole. The code counts NFA, not the size of the opening and not the airflow a brochure promises. A ridge vent is sold by the linear foot and rated per foot; a box vent (roof louver, turtle vent, slant back) is rated per piece. That single difference drives the whole comparison: ridge vent capacity grows with the length of the ridge, box vent capacity grows with the number of holes you are willing to cut.
Air Vent puts the trade-off in its own ridge vent brochure: 42 feet of ridge vent does the work of 15 roof louvers or 5 wind turbines. The arithmetic holds up against the ratings above — 42 feet at 18 in² is 756 in², fifteen 50 in² louvers is 750 — and it is the fastest rule of thumb on a ladder: one 50 in² box vent equals a little under three feet of ridge vent. Note how wide the ridge range is. A rolled vent at 12 in²/ft needs half as much length again as a 4-foot shingle-over section at 18, so the product on the truck matters as much as the vent type.
The code floor is 1/150 of the ventilated attic floor area in net free area. It drops to 1/300 in two cases: a Class I or II vapour retarder on the warm side of the ceiling in Climate Zones 6, 7 and 8, or when 40 to 50 per cent of the required area sits in the upper part of the attic, no more than 3 feet below the ridge measured vertically, with the rest supplied low. Both Air Vent and Lomanco split it evenly — half intake, half exhaust — so the exhaust vent you are choosing carries half the total. On a 1,500 sq ft attic that is:
| 1,500 sq ft attic | At 1/150 | At 1/300 |
|---|---|---|
| Total NFA required | 1,440 in² | 720 in² |
| Ridge vent at 20 in²/ft (VentSure 12 in) | 36 ft | 18 ft |
| Ridge vent at 18 in²/ft (ShingleVent II) | 40 ft | 20 ft |
| Rolled ridge vent at 12 in²/ft | 60 ft | 30 ft |
| Box vents at 60 in² (Lomanco 600) | 12 | 6 |
| Box vents at 50 in² (Lomanco 750, Airhawk SLA) | 15 | 8 |
| 12 in turbines at 95 in² | 8 | 4 |
| Exhaust half to place | 720 in² | 360 in² |
Every count is rounded up — Lomanco’s own sizing article rounds 9.6 vents to ten — and the intake side is sized to match or slightly exceed whatever exhaust NFA you actually install. The attic ventilation calculator runs the same arithmetic with your own floor area and splits out the soffit side.
Feet of ridge vent needed is only half the check; the other half is feet of ridge available. Air Vent’s install sheet stops the slot 6 inches short of each end wall or hip intersection and 12 inches either side of a chimney, so you lose a foot off every ridge before anything else. On a gable roof that hardly matters. On a hip roof it decides the job, because an equal-pitch hip on a rectangle has a ridge only as long as the footprint’s length minus its width.
The 50 × 30 ft gable has 49 feet of slot — room for 882 in² at 18 in²/ft against a 720 in² requirement. The hip on the same footprint has 19 feet: 342 in², short of 720 and short even of the 360 needed at 1/300. That is where box vents win. Fifteen Lomanco 750s set at one height, high on the rear and side slopes, carry the full 1/150 exhaust with no ridge vent at all. Air Vent also makes a shingle-over vent for diagonal hips rated at 12 in²/ft; read its own install sheet before pairing it with anything. The roof-shape side of this is on hip vs gable roof.
Attic floor area, the ratio you are building to, and the ridge length you can measure. Pre-filled with the 1,500 sq ft hip roof from the worked example.
Ridge falls short
342 in² available over 19.0 ft of slot · 720 in² of exhaust needed
| Exhaust option | Quantity |
|---|---|
| Exhaust NFA needed (half the total) | 720 in² |
| Ridge vent needed | 40 ft |
| Ridge you can slot | 19.0 ft |
| 12 in turbines instead | 8 |
| Box vents instead | 15 |
Pick one row, not two. Whichever exhaust you choose carries the whole high half on its own.
Count the slot, not the vent
The vent runs end to end for looks; only the length over an open slot ventilates. A ridge vent quoted at 50 feet over a slot cut 40 feet long is a 40-foot ridge vent.
No — and this is the one point every ventilation maker agrees on in writing. Air Vent’s static vent install sheet opens with it: install only one type of attic exhaust vent to avoid short-circuiting the system, do not mix wind turbines, ridge vents, gable louvers, roof louvers and power fans, and if another type already exists, remove it or plug its opening. Lomanco prints the same rule on its boxes as the second of its three must-do steps, and gives the reason: exhaust vents pull air from the easiest source, so with two types on one attic one of them ends up acting as intake for the other.
Picture what that means on the roof. A ridge vent sits at the peak; a box vent sits two feet down the slope. The ridge vent pulls, and the nearest opening is not the soffit thirty feet away but the box vent beside it. Air comes in through the louver, out through the ridge, and the attic floor between the eave and the ridge barely moves. Worse, a box vent drawing in is a box vent drawing rain and snow in — Lomanco’s first step, all exhaust at one height, exists for exactly that reason.
The commonest re-roof mistake
New ridge vent cut in, old box vents left in place “for extra airflow”. The ridge then breathes through the louvers, not the soffits. Gable-end louvers count too: Air Vent lists them among the exhaust types not to mix with a ridge vent.
A turbine is a box vent with a rotor on top. Air Vent lists its 12-inch turbine at 95 in² of net free area and the 14-inch at 132 in²; Lomanco says its 14-inch Big Whirlybird moves 37 per cent more air than its 12-inch and that the head is tested to withstand 110 mph winds. Wind spinning the head helps it pull, but the code sizes a turbine on its NFA like any other vent, so on paper one 12-inch turbine is worth just under two 50 in² box vents. What a static vent does not have is a moving head on bearings, a larger 12- or 14-inch hole, and the most visible profile on the roof. The mixing rule applies with full force — a turbine is a strong exhaust, and next to a ridge vent it simply pulls from the ridge.
A ridge vent is one long opening at the most exposed line on the house, so the design of the vent carries the weather risk. Air Vent warns that unbaffled ridge vents let wind blow straight through, or in one side and out the other; the baffled, filtered shingle-over types use an external baffle to throw rain and snow over the vent and an internal filter to catch fine snow. With architectural shingles Air Vent wants the gap between vent and shingle sealed without plugging the drain holes. Listed pitch for the 12-inch ShingleVent II and the VentSure strip is 3/12 to 16/12.
A box vent is a flashed penetration, and fifteen of them are fifteen more flanges to keep tight. Air Vent’s sheet tucks the upper half of the flange under the shingles, laps shingles over it down to the bottom of the opening, and calls for at least 8 galvanized nails with sealant over each one. Skip any of that — a flange face-nailed over the course above it, or sealant doing the flashing’s job — and the vent becomes the leak. When one does leak, it is traced and priced like any other penetration on the roof leak repair cost guide, and both vent types belong on the ridge zone of a roof inspection checklist.
Tear-off is the cheapest moment to change exhaust type, because the deck is bare and the old louver holes can be patched with new sheathing instead of capped. For a ridge vent, Air Vent cuts the slot 3/4 inch either side of the ridge centreline or the ridge board, snapped with a chalk line, plumb-cut, stopped 6 inches from end walls and hips; in cold weather it leaves a 1/8 inch gap between vent sections for expansion. For box vents, the hole centre goes 2 feet (maximum 3) down from the ridge, the vents evenly spaced and placed so they show from one side of the roof only. That puts them comfortably inside the code’s 3-foot vertical limit for upper vents.
Whichever you pick, the intake side has to be there to feed it. Baffles at every rafter bay and clear soffits are what make either exhaust work, and what keep the eave cold enough to stop the cycle described in the ice dam prevention guide. Heat trapped under the deck in summer is the other cost — it is the first thing on the list in how long asphalt shingles last, and Air Vent notes that most shingle warranties require proper ventilation to stay valid.
Buying checklist
Total NFA, the intake and exhaust split, feet of ridge vent.
The roof shape that decides how much ridge you get.
Why the intake half matters as much as the exhaust.
Tracing and pricing a leak at a vent flange.